30
FORCE A MANUAL EXHAUST FILTER CLEANING
If running the unit with the exhaust filter cleaning function disabled, the “DPF Status” screen may display a red alarm,
prompting the operator to force a manual exhaust filter cleaning. Use the following procedure to force a manual
exhaust filter cleaning feature:
1. Open the control door and locate the switch labeled “Auto Exhaust Filter Cleaning.”
2. Move and hold the rocker switch into the “ON / FORCED (I)” position for five seconds.
3. Toggle to the “DPF Status” screen on the Power Zone™ controller and verify the Regeneration indicator
appears above the words “DPF Lamp” (refer to “Diesel Exhaust Filter Monitoring” on page 23 for
information regarding the “DPF Status” screen and indicators).
ENABLE EXHAUST FILTER CLEANING
If the environment no longer requires the function to be disabled and there are no alarms present on the “DPF Status”
screen, the auto exhaust filter cleaning function should be enabled. Use the following procedure to enable the auto
exhaust filter cleaning feature:
1. Open the control door and locate the switch labeled “EXHAUST FILTER CLEANING.”
2. Move the switch into the “ON / AUTO (I/O)” position.
Toggle to the “DPF Status” screen on the Power Zone™ controller and verify the Regeneration indicator appears
above the words “DPF Lamp” (refer to “Diesel Exhaust Filter Monitoring” on page 23 for information regarding the
“DPF Status” screen and indicators).
POWER ZONE™ CONTROLLER INFORMATION DISPLAYS, FUNCTIONS, AND RESET
The Power Zone™ controller constantly monitors vital generator and engine functions for a number of operation,
alarm and fault conditions. When a fault condition occurs, the engine will shut down automatically and the main
display will show the fault that has caused the shutdown. To resume operation, the fault condition must be resolved.
To reset the controller and resume operation, press the Enter “” button.
RESETTING THE MAINTENANCE ALARMS
The Power Zone™ controller will display a warning message when the unit is due for maintenance or service. The
maintenance or service interval is set at 500 hours of engine running time. Once the unit has been serviced, the
“Maintenance Alarm” reminder needs to be reset. The following procedure demonstrates how to reset the running
hours to zero:
1. With the unit shut down, move the control power switch to the “CONTROL ON/I” position. After initialization, the
controller will toggle automatically to the Home screen.
2. Press any directional arrow (“”, “”, “”, “”) to enter the Maintenance screens.
3. Press the Enter “” button and the Engine Stop/Reset “O” button simultaneously. The next screen will display
the Configuration Menu.
4. Press “” to move the cursor (blue highlighted text) down to the “Maintenance” group.
5. Press “” to access the sections. Press “” to highlight the “Maintenance” section.
6. Press “” to access the parameters and highlight the maintenance alarm that needs to be reset.
7. Press the Enter “” button to select the editable parameters. The cursor will highlight “Not Reset” under the
selected maintenance alarm. Press ” to highlight “Reset”.